ABB TF42-13 Thermal Overload Relay
The TF42-13 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Further features are the temperature compensation, trip contact (NC),
Dimensions
Feature | Specification |
---|---|
Product Net Width | 45 mm |
Product Net Height | 88.3 mm |
Product Net Depth / Length | 70.5 mm |
Product Net Weight | 0.13 kg |
Technical
Feature | Specification |
---|---|
Setting Range | 10 … 13 A |
Rated Operational Voltage | Auxiliary Circuit: 600 V AC/DC Main Circuit: 690 V AC / 600 V DC |
Rated Operational Current (Ie) | 13 A |
Rated Frequency (f) | Auxiliary Circuit: 50 Hz / 60 Hz / DC Main Circuit: 50 Hz / 60 Hz |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit: 6 kV Main Circuit: 6 kV |
Rated Insulation Voltage (Ui) | 690 V |
Number of Poles | 3P |
Number of Auxiliary Contacts NC | 1 |
Number of Auxiliary Contacts NO | 1 |
Number of Protected Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC: 6 A Auxiliary Circuit NO: 4 A |
Rated Operational Current AC-15 (Ie) | (120 V) NC: 3 A / NO: 0.5 A (240 V) NC: 3 A / NO: 0.5 A (400 V) NC: 0.75 A / NO: 0.5 A (500 V) NC: 0.75 A / NO: 0.5 A |
Rated Operational Current DC-13 (Ie) | (24 V) NC: 1.25 A / NO: 1.25 A (60 V) NC: 0.55 A / NO: 0.55 A (125 V) NC: 0.55 A / NO: 0.55 A (250 V) NC: 0.27 A / NO: 0.27 A (500 V) NC: 0.15 A / NO: 0.15 A |
Degree of Protection | IP20 |
Pollution Degree | 3 |
Connection Details
Feature | Specification |
---|---|
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule: 1/2x 0.75 … 2.5 mm² Flexible with Insulated Ferrule: 1x 0.75 … 2.5 mm² Flexible with Insulated Ferrule: 2x 0.75 … 1.5 mm² Flexible: 1/2x 0.75 … 1 mm² Flexible: 1/2x 1 … 2.5 mm² Rigid: 1/2x 0.75 … 4 mm² |
Connecting Capacity Main Circuit | Flexible with Ferrule: 1/2x 0.75 … 4 mm² Flexible with Insulated Ferrule: 1/2x 0.75 … 4 mm² Flexible: 1/2x 0.75 … 4 mm² Rigid: 1/2x 0.75 … 4 mm² |
Tightening Torque | Auxiliary Circuit: 1 … 1.2 N·m Main Circuit: 1.5 … 2.5 N·m |
Wire Stripping Length | Auxiliary Circuit: 9 mm Main Circuit: 12 mm |
Recommended Screw Driver | Main Circuit: Pozidriv 2 |
Power & Suitability
Feature | Specification |
---|---|
Power Loss | At Rated Operating Conditions per Pole: 1.3 … 2.2 W |
Suitable For | AF09, AF12, AF16, AF26, AF30, AF38 |
Standards & Certification
Feature | Specification |
---|---|
Standards | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L |
Maximum Operating Voltage UL/CSA | Main Circuit: 600 V AC |
Contact Rating UL/CSA | (NC) B600, Q600 (NO) Q600, D300 |
Connecting Capacity Main Circuit UL/CSA | Flexible: 1/2x 18-10 AWG Stranded: 1/2x 18-10 AWG |
Connecting Capacity Auxiliary Circuit UL/CSA | Flexible: 1/2x 18-12 AWG Stranded: 1/2x 18-12 AWG |
Tightening Torque UL/CSA | Auxiliary Circuit: 9 … 11 in·lb Main Circuit: 13 … 22 in·lb |
Environmental
Feature | Specification |
---|---|
Ambient Air Temperature (Operation) | -25 … +60 °C |
Ambient Air Temperature (Operation Compensated) | -25 … +60 °C |
Ambient Air Temperature (Storage) | -50 … +80 °C |
Ambient Air Temperature Compensation | Yes |
Maximum Operating Altitude Permissible | 2000 m |
Resistance to Shock (IEC 60068-2-27) | 11 ms Pulse 25g |
Resistance to Vibrations | 5g 3 … 150 Hz |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Toxic Substances Control Act – TSCA | TSCA Declaration for Contactors |
There are no reviews yet.